Water management – securing water resources for municipal infrastructure needs.
Hot water buffer tanks
Heat buffers and 3 and 6 bar buffer tanks for industrial, heating and process installations.
CGH hot water storage tanks are used to store thermal energy in the form of hot water and to stabilise installation operation. They are applied wherever continuous heat availability, reduced temperature fluctuations and more efficient use of energy sources are important.
We design and manufacture vertical, aboveground, single-skin tanks in 3 and 6 bar versions. The design can be adapted to the installation parameters, required capacity, foundation method, insulation and nozzle arrangement.
CGH – water storage at the highest level!
CGH storage tanks are used in many sectors, including:
Industry – storage of technological and process water.
Fire protection systems – reserve water for firefighting.
Commercial and residential facilities – retention and use of rainwater.
Hot water storage in energy systems.
Purpose and advantages of CGH tanks
Hot water storage tanks act as a buffer between the heat source and energy consumers. They allow surplus heat to be accumulated and used when the installation demand increases.
This solution helps reduce temperature fluctuations, improves the operating stability of heat sources and supports efficient energy management across the entire system. The tank can be designed as part of a new installation or as an element of an existing system upgrade.
Large capacities and the possibility of adapting the tank to a specific installation.
3 and 6 bar versions for heating and process installations.
Manufacturing in accordance with PED and AD 2000 requirements.
Execution variants
| Variant | Standard | Design temperature | Construkction |
|---|---|---|---|
| 3 bar, wind 25 m/s | AD 2000 / PED | -10°C / +110°C | vertical,single-skin, on tubular legs |
| 3 bar, wind 35 m/s | AD 2000 / PED | -10°C / +110°C | vertical, single-skin, on support skirt |
| 6 bar, wind 25 m/s | AD 2000 / PED | -10°C / +110°C | vertical, single-skin, on tubular legs |
| 6 bar, wind 35 m/s | AD 2000 / PED | -10°C / +110°C | vertical, single-skin, on support skirt |
*Other variants, including 10 and 16 bar, available upon individual customer request
The selection of a variant depends on the required design pressure, foundation conditions and structural assumptions for the specific location. Tanks can be designed as structures on tubular legs or on a support skirt, depending on installation parameters and environmental loads.
Photos
Basic technical parameters
- Standard execution in P355GH material, with the option of using acid-resistant stainless steel upon customer request.
- Foundation: tubular legs or support skirt
- Thermal insulation: mineral wool, 100-300 mm (density 80-100 kg/m3)
*Other configurations available on request.
Available basic capacities of hot water buffer tanks
| CAPACITY [m³] | DIAMETER [mm] | TANK HEIGHT [mm] |
|---|---|---|
| 10 m³ | Ø2000 | 4400 |
| 24 m³ | Ø2500 | 4000 |
| 34 m³ | Ø2500 | 6000 |
| 43 m³ | Ø2500 | 8000 |
| 53 m³ | Ø2500 | 10000 |
| 63 m³ | Ø2500 | 12000 |
| 73 m³ | Ø2500 | 14000 |
| 32 m³ | Ø2900 | 4000 |
| 45 m³ | Ø2900 | 6000 |
| 59 m³ | Ø2900 | 8000 |
| 72 m³ | Ø2900 | 10000 |
| 85 m³ | Ø2900 | 12000 |
| 98 m³ | Ø2900 | 14000 |
| 111 m³ | Ø2900 | 16000 |
| 40 m³ | Ø3200 | 4000 |
| 56 m³ | Ø3200 | 6000 |
| 72 m³ | Ø3200 | 8000 |
| 88 m³ | Ø3200 | 10000 |
| 104 m³ | Ø3200 | 12000 |
| 120 m³ | Ø3200 | 14000 |
| 136 m³ | Ø3200 | 16000 |
| 46 m³ | Ø3400 | 4000 |
| 64 m³ | Ø3400 | 6000 |
| 82 m³ | Ø3400 | 8000 |
| 100 m³ | Ø3400 | 10000 |
| 118 m³ | Ø3400 | 12000 |
| 136 m³ | Ø3400 | 14000 |
| 154 m³ | Ø3400 | 16000 |
| 172 m³ | Ø3400 | 18000 |
| 190 m³ | Ø3400 | 20000 |
| 208 m³ | Ø3400 | 22000 |
| 180 m³ | Ø3800 | approx. 19380 |
*Other dimensions available upon individual order.
Example of a special execution
CGH also delivers hot water storage tanks outside the standard range. One example is a vertical aboveground tank with a nominal capacity of 180 m³, design pressure of 16 bar and design temperature of -20°C / +110°C, manufactured with thermal insulation, nozzles, inspection manhole, ladder and service platform.
Example project: vertical buffer tank 180 m³, 16 bar
| Parameter | Value |
|---|---|
| Type | vertical, aboveground, single-skin |
| Nominal capacity: | 180 m³ |
| Gross capacity: | approx. 203 m³ |
| Design pressure: | 16 bar |
| Design temperature: | -20°C / +110°C |
| Material | P355 |
| Diameter: | 3800 mm |
| Height: | approx. 19 380 mm |
| Weight without insulation: | approx. 37 274 kg |
| Insulation: | mineral wool 200 mm, 80 kg/m³ + aluminium cladding |
| Equipment: | DN500 manhole, 2 × DN300, drain, vent, temperature sensor connections, ladder, platform |