CGH is a manufacturer of industrial steel tanks that has supplied solutions for standby power and data centres for many years. CGH belly tanks are rectangular, double-wall fuel tanks installed directly beneath a generator set or container, or alongside the unit.
Ethanol storage tanks
Belly tanks
They store diesel or HVO and give the generator set the run-time autonomy required by the facility design. We design each tank for a specific generator set: its footprint, weight, fuel connection layout and required run time.
We produce tanks in standard container sizes as well as in dimensions specified by the customer.
Applications of CGH belly tanks
CGH belly tanks are used for:
Data centres and critical infrastructure: fuelling generator sets in data centres, hospitals and critical infrastructure facilities.
Emergency power: fuel storage for emergency power systems (UPS + generator set).
Diesel and HVO: storage and distribution of diesel and HVO.
Limited space: temporary and permanent solutions where space is limited.
Construction sites, mines, industry: fuelling containerised generator sets on construction sites, in mines and at industrial sites.
We adapt our designs to the specific nature of our customers’ production processes.
Purpose
By choosing CGH belly tanks, you get:
A load-bearing structure designed for the weight of the generator set or container.
Double-wall construction with interstitial space monitoring.
A compact, rectangular shape that takes up no additional floor space.
Compliance with EN 1090 and the legal requirements for fuel storage.
The option of stainless or acid-resistant steel construction.
Technical data of CGH belly tanks
Description:
- Rectangular single- or double-wall tanks made of S235JR steel (optionally stainless steel 1.4301/1.4307 or acid-resistant steel 1.4404).
- Ribbed load-bearing structure designed to support a generator set or container on the tank lid.
- Optional sloped bottom with a drain nozzle for removing water and sediment.
- The number, size and location of fittings are agreed with the customer at the design stage.
- Electronic leak detection system for the interstitial space.
- Tanks are manufactured in accordance with EN 1090.
Material:
Wall construction:
Dimensions:
External finish:
* Other configurations available on request.
CGH belly tanks – standard equipment
- inspection manhole with cover
- nozzles: filling, fuel suction and return, vent
- interstitial space nozzles
- transport lugs
- plate or frame for mounting the generator set
CGH belly tanks – optional equipment
- Interstitial space monitoring with alarm signalling.
- Fuel level measurement system with output to BMS.
- Overflow valve and fill-level indicator.
- Fuel polishing system (fuel circulation and cleaning) for long-term storage.
- Filtration system.
- Tank heating and insulation.
- Specialist anti-corrosion coatings C4M/H, C5M/H and internal coatings.
- Customised dimensions and colours, customer logo on the casing.
External tank surface
The external surface is shot-blasted to cleanliness grade Sa 2.5 to PN-ISO 8501-1 and protected with an anti-corrosion coating in class C3M or higher. Shot blasting and painting are carried out in the CGH paint shop, a 2,600 m² hall with temperature- and humidity-controlled booths.
Why choose CGH belly tanks
Safety: the double wall and continuous interstitial space monitoring protect the ground and the facility from fuel leaks.
Load capacity: a structure calculated for the weight of the generator set, the container and the dynamic loads from engine operation.
Space saving: the tank acts as the foundation for the generator set – it requires neither a separate footprint nor a containment bund.
Fuel quality: the fuel polishing and filtration system maintains the quality of diesel and HVO during long-term storage.
Flexibility: dimensions, fittings and equipment are selected for the specific generator set model.
Completeness: belly tanks can work with larger underground double-wall tanks to form a complete emergency power supply system.
Indicative belly tank capacities
| Usable capacity [m3] | Width [mm] | Length [mm] | Height [mm] |
|---|---|---|---|
| 6.1 | 2 438 | 6 058 | 600 |
| 16.0 | 3 200 | 9 000 | 800 |
| 17.0 | 3 640 | 12 730 | 530 |
| 18.4 | 3 600 | 12 300 | 600 |
| 18.5 | 2 438 | 9 125 | 1 200 |
| 21.6 | 3 000 | 13 000 | 800 |
| 28.4 | 3 200 | 16 000 | 800 |
| 29.1 | 3 000 | 14 000 | 1 000 |
| 29.1 | 4 000 | 13 110 | 800 |
| 33.4 | 3 000 | 14 600 | 1 100 |
| 37.9 | 3 900 | 20 000 | 700 |
| 39.4 | 2 438 | 12 192 | 1 910 |
| 44.6 | 4 000 | 14 602 | 1 100 |
* Usable capacity is given. Other sizes are available on request, including tanks for standard 20 ft and 40 ft containers and tanks with non-standard footprints tailored to customer requirements.
Indicative generator set run time from a belly tank
| Generator set rating [kVA] | Consumption at 100% load [l/h] | Fuel for 24 h [m3] | Fuel for 48 h [m3] |
|---|---|---|---|
| 500 | approx. 100 | approx. 2.4 | approx. 4.8 |
| 1 000 | approx. 200 | approx. 4.8 | approx. 9.6 |
| 2 000 | approx. 400 | approx. 9.6 | approx. 19.2 |
| 3 000 | approx. 600 | approx. 14.4 | approx. 28.8 |
* Indicative values at a consumption of approx. 0.25 l/kWh. We size the capacity based on the generator set data sheet and the facility’s required autonomy.
See also – Data Centre
Belly tanks are part of the complete CGH offer for data centres and emergency power. Check out the other solutions in this category:
- Belly tanks – rectangular steel tanks for diesel and HVO, with an example project.
- Cylindrical tanks for fuelling generator sets – double-wall above-ground tanks, also skid-mounted, with a pump system.
- Underground tanks – double-wall main tanks that supply belly tanks where fuel demand is high.
- Diesel tank in a container – mobile fuel storage within a container footprint.
CGH Mission we build trust, we deliver quality!
Our goal is to create innovative products that meet the demands of today’s market. We strive to ensure that CGH solutions contribute to environmental protection while supporting the growth and operational stability of your business.
CGH is a partner you can trust, regardless of the scale or complexity of your project.
Contact Us!
Do you have questions?
Would you like to learn more about our products?
Our team will be happy to answer all your questions and help you find the best solution for your needs.